• Arcanepotato@crazypeople.online
    link
    fedilink
    English
    arrow-up
    3
    ·
    10 hours ago

    Transformers take one voltage and make it a different voltage in the same box. The code doesn’t have a standard way of labelling the arc flash hazards, which means you get stupid things like the original picture.

    The primary and secondary can be in different enclosures. I agree the sticker config does not make sense for something with two enclosures.

    I do think your explanation is a little off, even if it is in one enclosure. Shock hazard and arcflash hazard analysis is independent, as are the PPE requirements. You need to account for both when planning work. The Shock hazard PPE only looks at the voltage of the system (see table 130.7©(7)(a)) whereas arcflash PPE needs to be suitable for the incident energy at the distance they will be performing their task. There is no overlap in the assessment.

    The pictured stickers are kind of shitty because they do not clearly show that Arcflash and Shock hazards are different types of hazards and different types of incidents.

    I’m more used to stickers like the one shown on this handy guide: https://www.70econsultants.com/Downloads/RozelLabelPosterv8.pdf

    Here we have the primary side saying if you are more than 26" away you aren’t required to wear shock protection PPE (restricted approach) but that you are still at risk of 2nd degree burns from an arc flash within 30" . You can still get shocked up to the limited approach (60") but you aren’t required to wear PPE. Approach boundaries are from table 130.4(E)(a). This distance is consistent with an exposed circuit at the given voltage (rather than a moving contactor).

    Additionally, incident energy is calculated at the distance the worker would be from the arc source when performing a task. That is why the primary side has the incident energy at 36" which is outside of the boundary, and why the 0 class (no protection) is indicated. And why you need to read the report and not just rely on the stickers! It would list the tasks and how everything is calculated.

    On the secondary side the restricted approach is 12", again consistent with the table in NFPA70E. In terms of arc flash it is saying the worker would be 18" from the source when doing the work, and that it is impossible to do safely. We don’t know the particulars of the design of this transformer so we can’t say why it’s 36" on one side and 18" on the other. The secondary sticker is basically saying there is no safe way to work live, regardless of shock protection, because the arcflash incident energy is too high.

    The code books don’t standardize how to communicate the required PPE which makes people do stupid things like in this picture: show conflicting requirements for safety. Shitty labeling like this can kill someone, but its not necessarily wrong labeling because the code leaves it up to interpretation.

    I also disagree with this. The code specifies that you must meet both the Arcflash and the Shock hazard PPE requirements if you are within the specified distances (130.7©(1) a and b). If it’s in one enclosure you are subject to the Arcflash PPE within the boundary radius of the arcflash source, and there is no way you are outside of the radius for the secondary side when working on the primary side. Discussion of gloves is moot because we are not taking the cover off this thing, but they are required to do the analysis anyways.

    Workers are not meant to rely only on the stickers. It’s the last line of defense and meant to be a sanity check on site. The workers in charge are required (by the code) to complete a job safety plan for each work task. If you come to site and your work plan has different boundaries than on the stickers, you know something is wrong.

    • A_be_seedy@beehaw.org
      link
      fedilink
      English
      arrow-up
      2
      ·
      9 hours ago

      The primary and secondary can be in different enclosures.

      Thus is true. In which case the labels should be applied to the separate enclosures.

      I agree the sticker config does not make sense for something with two enclosures.

      Glad we agree.

      Shock hazard and arcflash hazard analysis is independent, as are the PPE requirements. You need to account for both when planning work. The Shock hazard PPE only looks at the voltage of the system (see table 130.7©(7)(a)) whereas arcflash PPE needs to be suitable for the incident energy at the distance they will be performing their task.

      I agree with all of this. The nuance I’d add is that PPE needs to be suitable for the shock and incident energy they could receive while performing their task. The common field example would be the controls guy working on their low voltage DC inside a box with exposed 480v. Even if they 480v is further than 42" away from the control part they’re working on, they should still be wearing gloves. Similar with arc flash boundaries. For my guys, I consider the arc flash danger to be a plane parallel to the enclosure door as opposed to a single part, which goes above and beyond NFPA70E, but is becoming more and more industry standard/consensus. Basically, if you enter an enclosure you need protection for all exposed parts.

      The secondary sticker is basically saying there is no safe way to work live, regardless of shock protection, because the arcflash incident energy is too high.

      I don’t think I disagreed with anything prior to this statement. But this is where your argument starts to fall apart. The arc flash boundary for the secondary side is 613 inches, or 51 feet. Since the labels are both placed on the outside of a single enclosure, and moreover, they are placed together (as opposed to one clearly on the primary side and one clearly on the secondary side). Because we don’t live in a fantasy land, we can assume that the transformer is not 51’ in any direction.

      This means that there is no working condition where you could be safe while working on the primary side and NOT exposed to the secondary side.

      PPE is the last line of defense. Administrative, engineering, etc. all come before PPE. And one of the biggest causes of error is human error. Meaning designs should be designed to limit human error.

      While drawings are important to look at, the reality is that not every maintenance worker will look at drawings. And especially during an outage or failure, steps are more likely to be skipped. To reduce errors, arc flash and shock hazard stickers should not have different information they should only list the highest required PPE or highest determination of PPE (as in highest voltage, and highest arc flash potential) of all internal components. It’s the same reason why MCCs and Distribution panels should only have one label - despite having breakers that technically have different incident energies. Oddly enough, the debate of placing different stickers only seems to exist around transformers (with some exceptions where distribution panels have cabinets that could isolate arc flash potential).

      The reality is that the stickers are technically a higher level of protection than simply PPE. They should be clear, and they should give clear direction. I cannot enter the primary side of this transformer without being exposed to the arc flash potential of the secondary side, so there is no reason to list the arc flash boundary of the primary side. The arc flash boundary of the transformer is the higher of the 2 boundaries, and it should be labelled as such. Similarly, you need class 2 gloves to protect you from the guts of the transformer. A transformer is one single device and should be treated as such. Control boxes have 480v and low vDC, we don’t go into the cabinet with no PPE just because we’re working on vDC.

      I do applaud the training of your plant though, it sounds like your guys have more awareness than many plants I’ve seen. But even with that training, you are introducing human error factors when you label like this.

      • Arcanepotato@crazypeople.online
        link
        fedilink
        English
        arrow-up
        1
        ·
        7 hours ago

        I think we are agreeing.

        When I said

        The secondary sticker is basically saying there is no safe way to work live, regardless of shock protection, because the arcflash incident energy is too high.

        I meant

        there is no working condition where you could be safe while working on the primary side and NOT exposed to the secondary side.

        It sounds like you all don’t have task specific job safety plans? I’m not blaming you, it’s a systemic problem at the management level. Elec is basically the only team that does this well tbh and I think it’s because the supervisor does not fuck around and will not take a management no for an answer. It helps that we are unionized.

        We have plans for routine work come out with work orders for PMs and we will do them for correctives as correctives come up and keep them on file.

        Let’s say we get a new equipment. We require the arc flash study before it’s delivered. We make sure it matches up with our expectations and then it will be used to create PMs. Like you said, there is no reason to work on this live so no PMs or correctives would have the team working on it live and they would all include switching orders and how to verify it has been deenergized. Anyone opening a panel without all that is getting sacked, and we make sure they know it.

        I should also be clear this isn’t my plant and we don’t label like this. It’s not a great label but I can see why someone did it (to show it was calculated for both sides) we especially if they are some fresh out of school engineer 😅

        No formal training, just good at finding the guy who likes to yap and following him around so I can learn all I can.

        • A_be_seedy@beehaw.org
          link
          fedilink
          English
          arrow-up
          1
          ·
          6 hours ago

          It sounds like you all don’t have task specific job safety plans?

          Depends where I’ve worked, what the task is, and how it’s structured.

          Data center? Yes, we had quadruple redundancy. Boring job.

          Auto plant? PMs, yes. Reactive? Sometimes, but if the line was down, we weren’t getting them printed out. The maintenance training program was incredible though, trained the troubleshooting process, even the dumbest could have written a work plan for any piece of equipment. All equipment had PPE requirements and showed LO locations and procedures. For reactionary work, work plan was quick chat with everyone involved, then follow SOP for de-energization, verify de-energization. The work was done up front similar to how you’ve described, but on every team. Nothing got missed.

          100 year old steel mill? PMs and only sometimes. Fun place to work, but that job was almost 100% fire fighting. Safety culture didn’t exist, especially when private equity took over lol. Early on had an untrained maintenance guy in street clothes operate a tripped breaker rated over 90 cal, he did not look to see what caused trip. That was when I was able to create a glove and training program lol. But that plant is the biggest reason why I’m against double labels. That plant hasn’t filled my position, and when I left, very little of it got delegated. The arc flash stickers are probably the last line of defense, I don’t think the drawings have been looked at since I left. That’s common in a lot of plants I visit at my new job, unfortunately.

          I’ve had arguments with arc flash study providers over it - unfortunately this isn’t necessarily a dumb new engineer - these are well seasoned vets. And double labels in a book, or on a drawing makes sense. But when you look at plants that do less than bare minimum safety, it highlights how important those stickers are. The well trained facilities with good safety culture will have drawings to get information that’s missed on the removed label (primary side incident energy). But safety culture can go to shit overnight, turnover, etc. Sticking with 1 label per enclosure ensures that the safety you provide on those stickers will outlast your program.

          Labeling requirements per NFPA70E are nominal voltage, arc flash boundary, incident energy or PPE category*, and minimum PPE requirements. I believe that minimum PPE requirements should be carried through entire enclosure, and adding that to the book would close the transformer debate. But I think its been unaddressed for too long that they should be adding a note specifically calling out transformers and DPs.

          *this requirement is why you’ll see a PPE level listed instead of a PPE category if the incident energy is precisely calculated